Starting Guide for controllers Atom series - 6U (6 DIN modules)

Atom Hydrogen

Atom Hydrogen

Atom Neon

Atom Neon

Atom Helium

Atom Helium

Atom Ferrum

Atom Ferrum

Atom Carbon

Atom Carbon

Atom Argon

Atom Argon

Modifications

Atom

Atom

Basic version

Atom N

Atom N

Connect wireless devices and enjoy the remote control access

Atom N + OLED-дисплей

OLED-display

Optional for Atom NConfigure and diagnose devices even without internet connection

Functional elements

Atom Carbon N with numbers
1. 9-48V DCpower supply
2. CAN bus ensures synchronized operationof all Atom series devices
3. Integrate 3rd party devicesusing RS-485 interface
4. 5V and 3.3V ports for sensors power supply
5. 12 multifunction input ports (9 in N modification)for temperature, air quality, water leakage sensors and switches connection
6. Buttons for navigation and control of the OLED display menu
7. Graphic OLED displayfor control and monitoring (optional for N modification)
8. Ethernet port for network connectionpossibility of remote control using the phone or voice assistants (N modification)


Outputs

Atom Hydrogen

Energy meterBuilt-in energy meter with the ability to accurately measure
voltage, current and power consumption
2 x 5A relaysfor connection of electrical devices
8 x i3-flex slotsslots for changeable modules connection

Atom Helium

Energy meterwith the ability to accurately
measure voltage, current and power
consumption
2 x 5A relaysfor connection of electrical devices
3 dimming outputsoutputs built on MOSFET bases
with built-in load control meter to control
AC loads
4 x 10A relayswith built-in load control
meter for connection of electrical devices

Atom Neon

4 x 5A relaysfor connection of electrical devices
8 dimming outputsoutputs built on MOSFET baseswith built-in load control meter to control DC loads

Atom Ferrum

Energy meterwith the ability to accurately
measure voltage, current and power
consumption
2 x 5A relaysfor connection of electrical devices
8 x 10A relayswith built-in load control
meter for connection of electrical devices

Atom Carbon

Energy meterwith the ability to accurately
measure voltage, current and power
consumption
2 x 5A relaysfor connection of electrical devices
6 x 16A relaysfor connection of electrical devices

Atom Argon

18 x 5A relaysfor connection of electrical devices

LED indications

Atom Carbon N with numbers

1. Input ports indication

2. Device status indication

3. LAN connection indication

4. Output ports indication

5. Output ports type and status indication

Technical specifications

Important! Technical specifications, wiring diagrams, input and output specifications and other technical information can be viewed on our website

Atom Hydrogen photo

Atom Hydrogen

The set of multifunction inputs and modular architecture of outputs allow to use this controller to solve any technical problems, even if these tasks provide periodic change of types of input signals and types of loads. Change the configuration of outputs and inputs in real time without any tools.

Atom Helium photo

Atom Helium

Provides the ability to change the lighting level of LED, halogen and incandescent lamps, both individually and in groups (up to 300W per channel). In addition to light control, Atom Helium is perfect for controlling devices such as garage doors, electric locks, pumps, actuators and more.

Atom Neon photo

Atom Neon

The name itself says that its main purpose is to control modern lighting devices such as LED strips, furniture lamps, low-voltage LED lamps and more.

Atom Ferrum photo

Atom Ferrum

The ideal solution for controlling powerful and inductive loads, such as lighting groups, pumps, fans, electric motors, controlled sockets.

Atom Carbon photo

Atom Carbon

Designed to work with high loads. Not only you can turn on powerful devices, but also conveniently organize managed outlets and even use them to control the input power groups.

Atom Argon photo

Atom Argon

Ideal for controlling a large number of low-power loads: thermal heads, devices with dry contact inputs (garage doors, impulse blinds), intermediate relays, emergency lighting, electric locks and more.

Installation guide

Security requirements

During installation and operation, observe the general rules of electrical safety regarding the use of electrical appliances, as well as the requirements of regulations on electrical safety.
It is strictly forbidden to disassemble the device under voltage!

Atom series controllers require pre-configuration:


1. For Atom Hydrogen only:

Illustration

Remove the housing cover that closes the i3-flex connectors to install changeable modules. Insert the modules in place, making sure each module is inserted correctly and securely in the connector. Close the lid.


2. Installation

Install the controller and power supply to the DIN rail. Make sure there are no signs of mechanical damage or condensation. If necessary, install additional switchboard equipment - contactors, circuit breakers, power supplies and other automation devices.


3. Power supply

Connect the power supply to the mains via the circuit breaker. Connect the power supply output to the controller's power connector.
Controller power connectors, sensor power outputs and load control outputs for easy installation are made in the form of removable connectors with screw terminals.

Illustration

Important! Although the controller has built-in protection against incorrect power connection, and in this situation will not fail, we recommend that you pay attention to the correct polarity when connecting.


4. i3-NET

 If your system uses multiple controllers, connect them to a i3-NET network. Install the end terminators included in the equipment kit at the ends of the bus.

i3-NET з'єднання


5. Energy meter

If you have an energy meter, connect the phase and neutral conductors with a voltage of 220V to the connectors marked "AC IN".

Illustration

Important! This connection is required for the built-in energy meter and AC dimmers (if available).


6. RS-485

If you have Modbus control devices, connect them to the bus and connect them to the RS-485 connector. Install the end terminators included in the equipment kit at the ends of the bus

i3-NET з'єднання


7. Sensors power supply

A 5V and 3.3V controller outputs are provided to power the sensors.
Important! If the system uses sensors or actuators with other operating voltages, use additional power supplies or the power supply that powers the controller. If the system uses several power supplies - connect their "negative" terminals to each other.


8. Input connections

Connect sensors, switches and other devices to the controller inputs. The inputs of the controller use connectors with spring-loaded contacts, which provides convenience and reliability of connection of conductors with a cross section up to 1.5 mm2.

Atom (Basic)

    • TYPE OF INPUT / # OF INPUT

    • 1-2

    • 3-9

    • 10-12

    • TYPE OF INPUT / # OF INPUT

    • TYPE OF INPUT / # OF INPUT

    • 1-2

    • 1-2

    • 3-9

    • 3-9

    • 10-12

    • 10-12

    • Analog (thermistor, photoresistor, etc.)

    • TYPE OF INPUT / # OF INPUT

    • Analog (thermistor, photoresistor, etc.)

    • 1-2

    • 3-9

    • 10-12

    • Digital (motion sensors, light level sensors, switches, buttons, etc.)

    • TYPE OF INPUT / # OF INPUT

    • Digital (motion sensors, light level sensors, switches, buttons, etc.)

    • 1-2

    • 3-9

    • 10-12

    • Interface (1-Wire sensors)

    • TYPE OF INPUT / # OF INPUT

    • Interface (1-Wire sensors)

    • 1-2

    • 3-9

    • 10-12

Modification Atom N

    • TYPE OF INPUT / # OF INPUT

    • 1-2

    • 3-9

    • TYPE OF INPUT / # OF INPUT

    • TYPE OF INPUT / # OF INPUT

    • 1-2

    • 1-2

    • 3-9

    • 3-9

    • Analog (thermistor, photoresistor, etc.)

    • TYPE OF INPUT / # OF INPUT

    • Analog (thermistor, photoresistor, etc.)

    • 1-2

    • 3-9

    • Digital (motion sensors, light level sensors, switches, buttons, etc.)

    • TYPE OF INPUT / # OF INPUT

    • Digital (motion sensors, light level sensors, switches, buttons, etc.)

    • 1-2

    • 3-9

    • Interface (1-Wire sensors)

    • TYPE OF INPUT / # OF INPUT

    • Interface (1-Wire sensors)

    • 1-2

    • 3-9

Dangerous interference can occur on long lines when connecting end devices such as switches, so we use additional protection and improved sensitivity of interaction with end devices. We use optocouplers for this. By default, all inputs with jumpers are configured in this mode "Optocoupler". If you use digital sensors at the inputs of the controller, be sure to turn off this mode.

Illustration

Without optocoupler (IN1-IN3)

Входи з оптопарою

With optocoupler (IN1-IN3)

Important! Inputs and “shared” outputs are signed. The common terminals are marked with the letter “G” and are connected to the “minus” power supply of the controller. All common contacts are interconnected, so when connecting switches with a lot of wired cable, it is enough to use only one connection to the “G” terminal.

Схема підключення давачів


9. Connect outputs

Connect the controller-controlled devices to the outputs. Each output is implemented in the form of a 2-pin connector and is designed to connect conductors with a cross section up to 2.5 mm2. One of the contacts is marked "OUT", to which the load is connected according to the type of output.
Examples of connecting loads to Atom 6U controllers on the example of Atom Hydrogen N are given below.

Схема пілключення LED-ламп

Important! Pay attention to the connection of DC devices. Negative polarity must be applied to the equipment. Also note that the load is connected directly to the OUT terminal


10. Network connection (modification N)

The operation of network controllers requires remote access to configure, manage and control their operation. To ensure these capabilities, at least one of the controllers must be able to connect to a wired or wireless network. In the Atom product line, these are the N modification controllers. Don't forget to connect the network cable to the controller or configure access to the home Wi-Fi network 

Підключення Ethernet-кабелю

Important! The router must have a DHCP server configured to automatically issue the IP address and network mask


11. Done. Turn on the power

Important! Check all connections. Make sure that the power supply, inputs and outputs are connected correctly.

i3 Home App Settings


1. Download i3 Home App


2. Once launched, the application offers to create an account to log in

Illustration


3. Set up a network (WiFi or LAN) and assign devices to the house

Illustration

● To do this, you must turn on the device● Register in the application and click "Go to settings" on the dashboard● Provide access to geodata in the application (necessary for bluetooth search)● Then on the device that appears, click "Configure network"● You will be prompted to create a PIN Code
Important! Remember the PIN Code - without it in the future it will be impossible to reconfigure Wi-Fi connection and connect the device to another home.
● Connect to a network (Wi-Fi or LAN) and provide access to the cloud.● If you have several identical devices, you can use the "Detect" function, the indicator on the device will start flashing, and you can give it a name so that you can easily find the desired device in the future.


4. Setting the date and time of controllers

Important! You do not need to configure each device on the network, when setting the time zone for one of the devices - it will be set on all the devices in the network.● In Device Manager, click the Configure button on any network device.In the menu, click "Date and time"● If the time zone is different from the current one (it will be displayed in red), select the desired one from the drop-down list or turn on the option "Use the time zone as on the phone"
Important! The time zone will be saved automatically when pressed and will not change later without manual reconfiguration.

Illustration


5. Devices settings

You need to specify what is connected to the ports (this will create devices that the user can control, such as a lamp or motion sensor).

Налаштування портів у додатку

Important! The devices have the function of auto-detection of modules or ports, the list of end devices that you can connect will depend on the type of port, for example, you can not install a dimmer lamp if the device has only a relay port type.


6. Creating automations

Once the devices are configured on the controller, we can control them using a mobile application and a voice assistant. But in order not to look for the phone every time and provide the usual ways of control, you need to configure automation.
To configure automation, go to the main window "Dashboard" and select "Automation" in the bottom panel

Перегляд існуючих автоматизацій у додатку

Similarly, you can configure all devices connected to the inputs and outputs of the controller, and set the rules of their interaction, and, for example, different options for pressing one switch, you can configure the response of different devices, running scripts and more. Conversely, the response of one device can be set to different switches (for example, the implementation of a master switch).

List of typical problems and their solutions

  • LED indicators do not light

    1. Check the supply voltage on the controller
    2. Check the polarity of the power supply

  • The device is turned on but not in the application settings

    1. Make sure Wi-Fi and bluetooth are turned on on your smartphone or tablet
    2. Verify that the home network password is specified correctly in the controller settings

  • Input indicators do not respond to signals from sensors or switches

    1. Check that the connection is correct
    2. Check that the connections at the controller and sensor terminals are secure
    3. Check the login configuration to the type of sensor or switch

  • Output status indicators are not lit

    Check that the output settings are correct in the controller settings

  • The output status indicator lights up, the device does not turn on, or responds incorrectly

    1. Check that the connection is correct and reliable
    2. Check the device for damage

Didn’t find the answer to your question?